TCI

Line reactors are current-rated devices. Therefore, in order to apply one, you simply need to know the full load AMPs of the drive with which it will be used and the amount of impedance that is necessary in the application.
| Recommended Impedance Levels |
- 3% eliminates bus overvoltage tripping
- 5% protects against physical damage to drive components and offers the most harmonic reduction.
- 1.5% is the recommended input minimum to protect the drive and is the recommended maximum impedance when the filter is used as an output device. (600V installations will see 20% lower impedance at rated current.)
| Impedance Rating - 480V 3%, 600V 2.4%, 240V 6% |
Part Number |
Standard Connection Type |
Termination Options |
Watts Loss |
Inductance (uH) |
AMPs |
|
| KLR2ATB (1) |
#12MAX |
QD/FL/ST |
8 |
11026 |
2 |
|
| KLR3ATB (1) |
#12MAX |
QD/FL/ST |
9 |
7351 |
3 |
|
| KLR4ATB (1) |
#12MAX |
QD/FL/ST |
15 |
5513 |
4 |
|
| KLR6ATB (1) |
#12MAX |
QD/FL/ST |
17 |
3675 |
6 |
|
| KLR8ATB (1) |
#12MAX |
QD/FL/ST |
27 |
2757 |
8 |
|
| KLR12ATB (1) |
#12MAX |
QD/FL/ST |
31 |
1838 |
12 |
|
| KLR16ATB (1) |
#4-#18 |
FL/RL |
38 |
1376 |
16 |
|
| KLR18ATB (2) |
#4-#18 |
FL/RL |
40 |
1225 |
18 |
|
| KLR25ATB (2) |
#4-#18 |
FL/RL |
48 |
882 |
25 |
|
| KLR35ATB (2) |
#4-#18 |
FL/RL |
70 |
630 |
35 |
|
| KLR45ATB (2) |
#4-#18 |
FL/RL |
74 |
490 |
45 |
|
| KLR55ATB (2) |
#4-#18 |
FL/RL |
113 |
401 |
55 |
|
| KLR80ATB (3) |
#4-#18 |
FL/RL |
129 |
276 |
80 |
|
| KLR110ACB (3) |
0.28" HOLE |
PT |
152 |
200 |
110 |
|
| KLR130ACB (3) |
0.28" HOLE |
PT |
148 |
170 |
130 |
|
| KLR160ACB (3) |
0.34" HOLE |
PT |
165 |
138 |
160 |
|
| KLR200ACB (4) |
0.38" HOLE |
PT |
222 |
110 |
200 |
|
| KLR250ACB (4) |
0.44" HOLE |
PT |
261 |
88 |
250 |
|
| KLR300ACB (4) |
0.44" HOLE |
PT |
291 |
74 |
300 |
|
| KLR360ACB (4) |
0.56" HOLE |
PT |
380 |
61 |
360 |
|
| KLR420ACB (4) |
0.53" HOLE |
PT |
400 |
53 |
420 |
|
| KLR480ACB (4) |
0.53" HOLE |
PT |
392 |
46 |
480 |
|
| KLR600ACB (4) |
0.53" HOLE |
PT |
493 |
37 |
600 |
Numbers in parenthesis indicate NEMA 1 cabinet size for the enclosed KLR option. This number should be added to the end of the standard KLR part number when ordering an enclosed KLR.
|
 |