Main Connection
| 3 Phase Supply Voltage: |
U2IN = 208...240 V ± 10 %
U3IN = 380...415 V ± 10 %
U5IN = 380...500 V ± 10 %
U6IN = 525...690 V ± 10 % |
|
| Frequency: |
48...63 Hz |
|
| Short Circuit Capacity: |
50 kA 1 s |
|
| Power Factor: |
cos1 = 0.97 (fundamental)
cos = 0.93...0.95 (total) |
|
Enclosure
| Degree of Protection: |
IP 21 (Standard for ACS 607)
IP 22 (Standard for ACS 601, Optional for ACS 607)
IP 42 (Optional)
IP 54 (Optional, derating required for ACS 601)
IP 54R (R = flange for air duct, optional only for frames R11i and larger) |
|
| Paint Color: |
ACS 601/604
Light beige NCS 1502-Y (RAL 90021/PMS 420C), Black ES 900
(ACS 601 Frame sizes R2...R6)
ACS 607
Light beige RAL 7035 semi gloss |
|
Motor Connection
| 3 Phase Output Voltage |
0...U2IN/3IN/5IN/6IN |
|
| Frequency Control |
0...±300 Hz
0...±120 Hz with du/dt filters |
|
| Field Weakening Point: |
8...300 Hz |
|
| Motor Control Software: |
ABB's Direct Torque Control (DTC) |
|
| Torque Control: |
Torque step rise time |
| Open Loop |
<5 ms with nominal torque |
| Closed Loop |
<5 ms with nominal torque
Non-linearity: |
| Open Loop |
±4 % with nominal torque |
| Closed Loop |
±1 % with nominal torque |
|
| Speed Control |
Static accuracy |
| Open Loop |
10 % of the motor slip |
| Closed Loop |
0.01 % of the nominal speed
Dynamic accuracy |
| Open Loop |
0.3...0.4 %sec. with 100 % torque step |
| Closed Loop |
0.1...0.2 %sec. with 100 % torque step |
|
Environmental Limits
| Ambient Temperature: |
Transportation: -40...+70 °C
Storage: -40...+70 °C
Stationary use: 0...+40 °C
(+50 °C by derating, see figure below) |
|
| Relative Humidity: |
5...95 %, no condensation allowed |
|
| Cooling Method |
Dry Clean Air |
|
| Altitude: |
0...1000 m ASL No derating required.
1000...4000 m ASL Derating required. |
Imax = IN,40C (100 % - 1 %  |
 |
+ x (40°C - Tamb)) |
| x |
= 1,5 % / °C ACS 607 |
| x |
= 3,5 % / °C ACS 601 |
| h |
= altitude above sea level > 1000 m |
| IN,40C |
= ACS 600 nominal current at 40 °C |
| Tamb |
= maximum ambient temperature, Note: Imax < or = IN,40C
|
|